vertiv GXT4 1000VA (900W) 230V RACK/TOWER UPS GXT4-1000RT230E
Get The Best vertiv ups Now From EGYPTLAPTOP - Vertiv Liebert Ups GXT4-1000RT230E
Liebert® GXT4™ is a real on-line UPS that delivers steady, high-quality AC energy to IT gear with no break when transferring to battery. It protects gear from nearly all energy disturbances as a consequence of blackouts, brownouts, sags, surges or noise interference. For sturdy safety Liebert GXT4 UPS fashions present trade main options in a compact design.
Advantages
-Compact 2U excessive RT design maximizes area for servers when rack is put in
-Controllable energy to a number of gadgets through two independently programmable pairs of sockets
-Lively ECO mode for elevated effectivity
-Consumer-friendly multi-language LCD show for straightforward entry to UPS knowledge
-0.9 output energy issue maximizes energetic energy offered
-Scorching swappable batteries and prolonged battery cupboards to extend availability
-Upkeep bypass choice for 100% uptime
-Glorious enter and output performances cut back TCO
-As much as six exterior battery cupboards for prolonged runtime
Options
-On-line double conversion UPS
-2U excessive all through the vary
-Two controllable socket teams
-Rotatable multi-language LCD show
-Lively ECO mode
-Replaceable hot-swappable batteries
-Automated frequency sensing
-Rack and tower mounting flexibility
-Optionally available bundle codes together with rack mounting equipment and SNMP/Webcard
-A number of communication choices (USB, RS232, SNMP, Modbus and Relay)
-Frequency conversion functionality
-Prolonged runtime
-ENERGY STAR® qualified
MODEL NUMBER: GXT4-1000RT230E
RATING: 1000VA/900W
Dimensions, D x Wx H, mm (in):
Unit: 408 x 430 x 85 (16.2 x 16.9 x 3.4)
Shipping: 617 x 570 x 262 (24.3 x 22.4 x 10.3)
Weight, kg (lb):
Unit: 18.2 (40)
Shipping: 24 (53); “E” model 20 (44)
Input AC:
Voltage Range: (typical) 230VAC nominal;
variable based on output load:
90% ~ 100% loading: 177VAC/280VAC
70% ~ 90% loading: 168VAC/280VAC
30% ~ 70% loading: 150VAC/280VAC
0 ~ 30% loading: 115VAC/280VAC
Frequency: 40Hz ~ 70Hz; Auto Sensing
Input Power Receptacle: C14
Output AC:
AC-AC Efficiency: > 88% AC-AC, minimum
Output Receptacles: C13 × 6
Voltage: 200/208/220/230/240VAC(user configurable); ±3%
Frequency: 50 Hz or 60Hz
Waveform: Sine wave
Mains (AC) Mode Overload: 200% for 2 seconds; 150% for 50 seconds with transfer to bypass
Internal Battery Charger:
Charger Current, Amperes: 1.3
Battery:
Type: Valve-regulated, non-spillable, lead acid
Qty × V× Rating: 4 × 12V× 5.0Ah
Battery Mfr/Part#: YUASA/NPH5-12; CSB/ HR 1221W; CSB/GP1245
Recharge Time 5 hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown
(InternalBatteries Only)
EnvironmentalRequirements
Operating Temp: 0ºC to +40ºC (+32ºF to +104ºF);
Storage Temp: -15ºC to +50ºC (5ºF to 122ºF)
Relative Humidity: 0%RH to 95%RH, non-condensing
Operating Elevation: Up to 3000 m (10,000 ft.) at 25ºC (77ºF) without derating
Storage Elevation: 15,240 (50,000 ft.) maximum
Audible Noise:
< 46 dBA, at 1 meter (3.2ft)from the rear
< 43 dBA, at 1 meter (3.2ft)from the front or sides
Agency:
Safety: IEC/EN/AS 62040-1:2008, GS mark; UL 1778 Listed
RFI/EMI: IEC/EN/AS 62040-2 2nd Ed (CategoryC2) = CISPR22 Class A
Surge Immunity: IEC/EN 62040-2 2nd Ed (IEC/EN 61000-4-5)
Transportation: ISTAProcedure 1A
LOAD
PERCENT OFCAPACITY
230 VAC RT MODELS : 1000VA
Internal Battery:
10% 88
20% 40
30% 31
40% 24
50% 17
60% 14
70% 11
80% 9
90% 8
100% 6